Multi-Zone Shielding in SESShield-3D

The new Multi-Zone shielding analysis capability in SESShield-3D allows for the analysis of a substation with multiple critical lightning currents with the Rolling Sphere Method in a single model, and displays a single, accurate, easy-to-understand graphical rendering of results, along with individual reports for each zone.

A zone is defined as folder node in the Construction Tree directly below the project-level node and the critical current for each zone can be independently defined, with all the specification methods already available in SESShield-3D.

Example Image
SESShield3D Construction Tree and Properties View.

Results from all zones are reported in a single image, ensuring that any area suffering from a shielding failure in any zone, represented with a red surface, is visible even if a protective surface from another zone would normally cover it.

Example Image
An example of a Multi-Zone case.
Example Image
Analysis results in the 3D-Viewer

A separate report is generated for each zone, so as many tabs as zones are created.

Example Image
A separate report is generated for each zone.